A power outage on a farm is more than an inconvenience. Cows still need milking, milk in the bulk tank must remain chilled, and heat and ammonia can rise quickly in a closed poultry house when its fans stop. Many rural farms sit at the end of long overhead lines, where outages can last longer and repairs may take more time.
This guide covers how to identify the farm loads a generator must support, what animal-welfare requirements apply to backup ventilation, how to size a generator for those loads, and how a tractor-driven PTO generator compares with a fixed standby unit. It draws on datasheet figures for the standby generators in our range and two real farm installations.
What does a farm generator need to run?
Begin with the equipment that protects animal welfare and the farm’s product, then exclude non-essential loads.
On a dairy farm, priority equipment includes the milking parlour’s vacuum pumps, milk pumps and controls; bulk milk tank cooling; cattle-shed ventilation fans; feed systems; and yard lighting and small power needs. Milk must stay cold in the bulk tank, or it may be rejected when collected.
On a poultry unit, priority equipment includes ventilation fans, automated feeding lines, lighting programmes and environmental controls, all of which rely on mains electricity throughout the day and night.
Typical running loads for common farm equipment include:
| Equipment | Typical running load | Notes |
|---|---|---|
| Milking vacuum pump | 4 to 7.5 kW | Start before other motors |
| Milk cooling compressors | 3 to 7.5 kW | Priority load, starting surge |
| Electric water heater | 3 to 6 kW | Steady load |
| Wash pump | 2 to 2.5 kW | Short surge |
| Feed auger or conveyor | 1.5 to 4 kW | Short surge |
| Grain dryer fan | 7.5 to 15 kW | Large starting load |
| Lighting, small power | 2 to 5 kW | Light load |
| Ventilation fans | Read from each fan's rating plate | Add up all fans on the circuit |
These are common ranges. For ventilation fans, use the values shown on your own equipment’s rating plates instead of depending on a general estimate.

What welfare rules require for backup ventilation
The Welfare of Farmed Animals (England) Regulations 2007 include several requirements in Schedule 1 that relate to backup power:
- Automated or mechanical equipment essential to animals’ health and wellbeing must be checked at least once daily.
- If animals’ health and wellbeing rely on an artificial ventilation system, an adequate backup must ensure sufficient air renewal if the system fails. An alarm must also function even when the main electricity supply is interrupted.
- The backup system must receive a thorough inspection, and the alarm must be tested, at least once every seven days.
The regulations do not prescribe how backup must be supplied; a standby generator is one common option. The full text is available at gensetplus.com. Wales, Scotland and Northern Ireland have their own equivalent regulations, so check the requirements for your farm’s location. This is general information, not legal advice. Your vet, assurance scheme or local authority can advise on the needs of your particular system.
Single-phase or three-phase?
Many farm buildings and smaller parlours use a single-phase supply, whereas larger parlours, grain dryers and high-powered motors often require three phase. Select a generator that matches the supply used by your essential loads.
- A three-phase set provides roughly one-third of its total capacity on each phase for single-phase loads. For instance, a 20 kVA three-phase set can supply around 6.7 kVA per phase at its prime rating.
- A single-phase set is a good fit for farms with single-phase supplies. Our range includes the Cummins C28D5-1P, rated at 22 kVA standby and 20 kVA prime at 230 V, and the Cummins C38D5-1P, rated at 30 kVA standby and 27 kVA prime.
How to size a farm generator
Follow these steps:
- List your priority loads and check each appliance’s rating plate for its running load in kW or amps.
- Identify the biggest starting load, often a vacuum pump, bulk tank compressor or dryer fan.
- Total the running loads that must operate at the same time, rather than every load on the farm.
- Keep a typical load below about 80% of the prime kW rating, leaving capacity for surges and future needs.
- Pick single or three phase to suit your electrical supply.
The table below illustrates how this applies to sets in our range, based on their prime ratings:
| Typical running load up to | Suggested size | Example model | Prime rating |
|---|---|---|---|
| About 13 kW | 20 kVA, three phase | Cummins C22D5 | 16 kW |
| About 19 kW | 30 kVA, three phase | Cummins C33D5 | 24 kW |
| About 22 kW | 30 kVA, single phase | Cummins C38D5-1P | 27 kW |
| About 32 kW | 50 kVA, three phase | Cummins C55D5EQ | 40 kW |
| About 38 kW | 60 kVA, three phase | Cummins C66D5EQ | 48 kW |
Worked examples for dairy farms
- A small dairy. A 4 kW vacuum pump, 3 kW milk cooler, 3 kW water heater and 1.5 kW of lighting add up to 11.5 kW—around 72% of the 16 kW available from a 20 kVA set. This is a suitable match.
- A medium dairy. A 5.5 kW vacuum pump, 4 kW cooler, 3 kW water heater, 2.2 kW wash pump, 1.5 kW of lighting and 2 kW feed auger use 18.2 kW in total, roughly 76% of a 30 kVA set's 24 kW capacity.
- A larger dairy. A 7.5 kW vacuum pump, 7.5 kW cooler, 6 kW water heater, 2.2 kW wash pump, 3 kW feed auger and 2 kW of lighting total 28.2 kW—about 70% of the 40 kW available from a 50 kVA set.
- Adding a grain dryer fan. The extra 15 kW fan brings the larger dairy's total to 43.2 kW. That is above a 50 kVA set's capacity and around 90% of a 60 kVA set's 48 kW. You could schedule the fan to run after milking, or select the larger generator.
Motor starting on a farm
Vacuum pumps, bulk tank compressors, augers and dryer fans can draw several times their normal running current when starting. As a general rule, a motor with direct-on-line starting should be no larger than roughly one-third of the generator's kW rating. This works out to about 5 kW on a 16 kW set, 8 kW on a 24 kW set, 13 kW on a 40 kW set and 16 kW on a 48 kW set. Soft starters can accommodate larger motors, and alternator design also affects performance, so confirm the specifications for the exact generator.

Expert tip: Use a consistent sequence when starting equipment: switch on the vacuum pump first, followed by the bulk tank compressors, rather than allowing all equipment to restart together when electricity returns. If the farm uses several large motors, discuss staged restarting or soft starters when choosing the generator.
PTO generator or standby set?
Many farmers compare a tractor-powered PTO generator with a permanently installed diesel standby set. Each option is better suited to different circumstances.
Worked examples for dairy farms
- A small dairy. A 4 kW vacuum pump, 3 kW milk cooler, 3 kW water heater and 1.5 kW of lighting add up to 11.5 kW—around 72% of the 16 kW available from a 20 kVA set. This is a suitable match.
- A medium dairy. A 5.5 kW vacuum pump, 4 kW cooler, 3 kW water heater, 2.2 kW wash pump, 1.5 kW of lighting and 2 kW feed auger use 18.2 kW in total, roughly 76% of a 30 kVA set's 24 kW capacity.
- A larger dairy. A 7.5 kW vacuum pump, 7.5 kW cooler, 6 kW water heater, 2.2 kW wash pump, 3 kW feed auger and 2 kW of lighting total 28.2 kW—about 70% of the 40 kW available from a 50 kVA set.
- Adding a grain dryer fan. The extra 15 kW fan brings the larger dairy's total to 43.2 kW. That is above a 50 kVA set's capacity and around 90% of a 60 kVA set's 48 kW. You could schedule the fan to run after milking, or select the larger generator.
Motor starting on a farm
Vacuum pumps, bulk tank compressors, augers and dryer fans can draw several times their normal running current when starting. As a general rule, a motor with direct-on-line starting should be no larger than roughly one-third of the generator's kW rating. This works out to about 5 kW on a 16 kW set, 8 kW on a 24 kW set, 13 kW on a 40 kW set and 16 kW on a 48 kW set. Soft starters can accommodate larger motors, and alternator design also affects performance, so confirm the specifications for the exact generator.

Expert tip: Use a consistent sequence when starting equipment: switch on the vacuum pump first, followed by the bulk tank compressors, rather than allowing all equipment to restart together when electricity returns. If the farm uses several large motors, discuss staged restarting or soft starters when choosing the generator.
| PTO generator | Diesel standby set | |
|---|---|---|
| Needs a person to start | Yes, hitch up, connect and run the tractor | No, with an automatic changeover it can start on its own |
| Ties up a tractor | Yes, for the whole outage | No |
| Output | Depends on tractor engine speed | Governed engine at a steady speed (1,500 rpm on our Cummins sets) |
| Best for | Occasional use where someone is always on hand | Unattended failures, nights and weekends |